Main features & overview

01 t4a

Overview

Description

  • Temperature limits: - 40 ... +250°C
  • Tolerance:
    Norme UNI 7938 standards, IEC 584.2 class 2:
    for types J, K: ± 2.5°C
  • Extension cable insulation: fibreglass, screened TEFLON ®
  • Eyelet thermocouple with low thermal profile and quick response time, suitable for measures on flat surfaces
  • Cable to DIN standard

Main features & overview

04 TC1

Overview

Description

  • Max. temperature limit: -40...+250°C (see table for thermocouple cable used)
  • Reference tolerances: Standards IEC 584.2 class 2 for type J, K: ± 2.5°C (-40...+333°C)
  • Cable to DIN standard
  • Highly versatile
  • Low cost

Main features & overview

05 tc3a

Overview

Description

  • Temperature limits: -40 ... +250°C
  • Tolerance:
    UNI 7938, IEC 584.2 Standards, Class 2:
    for types J, K: ± 2.5°C
  • Extension cable insulation: fibreglass, screened TEFLON ®
  • Stainless steel tip
  • Thrust spring washer
  • Cable to DIN standard

Main features & overview

03 tc6M

Overview

Description

  • Temperature limits:
    - 40 ... + 350° C for type T
    - 40 ... + 750° C for type J
    - 40 ... + 900° C for type E
    - 40 ... + 1000° C for type K
    (see table for sheath diameters)
  • Tolerance:
    IEC standard 584.2/Class 1:
    for type T:
    ± 0,5° C (- 40 ... + 125° C)
    ± 0.004 [t] (t > + 125° C)
    for type J, E, K:
    ± 1.5° C (- 40 ... + 375° C)
    ± 0.004 [t] (t > + 375° C)
  • Mineral insulated (MgO) thermocouple element and continuous metal sheath
  • Application versatility

Main features & overview

01 tc2 ac2

Overview

Description

  • Temperature limits:
    -40 ... + 350°C for type T
    -40 ... + 550°C for type J
    -40 ... + 600°C for type E
    -40 ... +1050°C for type K (see table for sheath diameters)
  • Tolerance:
    UNI 7938, IEC standards 584.2/Class 1:
    for type T:
    ± 0,5° C (- 40 ... + 125° C)
    ± 0.004 [t] (t > + 125° C)
    for type J, E, K:
    ± 1.5° C (- 40 ... + 375° C)
    ± 0.004 [t] (t > + 375° C)
  • Mineral insulated interchangeable insert
  • Application versatility

Main features & overview

03 tc6M

Overview

MgO amplified output - General purpose

Description

  • Amplified output signal o Temperature limits:
    -40 ... +350°C for type T
    -40 ... +750°C for type J
    -40 ... +900°C for type E
    -40 ... +1000°C for type K (see table for sheath diameters)
  • Tolerance:
    IEC 584.2 STANDARD class 1:
    or type T:
    ± 0,5° C (- 40 ... + 125° C)
    ± 0.004 [t] (t > + 125° C)
    or type J, E, K:
    ± 1.5° C (- 40 ... + 375° C)
    ± 0.004 [t] (t > + 375° C)
  • Mineral insulated (MgO) thermocouple element and continuous metal sheath
  • Application versatility

Main features & overview

01 tc2 ac2

Overview

Interchangeable MgO insert - Industrial processes and furnaces

Description

  • Amplified output signal
  • Temperature limits:
    -40 ... + 350°C for type T
    -40 ... + 550°C for type J
    -40 ... + 600°C for type E
    -40 ... +1050°C for type K
    (see table for sheath diameters)
  • Tolerance:
    UNI 7938, IEC standards 584.2 Class 1:
    for type T: ± 0,5° C (- 40 ... + 125° C)
    ± 0.004 [t] (t > + 375° C)
    for type J, E, K: ± 1.5° C (- 40 ... + 375° C)
    ± 0.004 [t] (t > + 375° C)
  • Mineral insulated interchangeable insert
  • Application versatility

Main features & overview

02 tc6 ac6

Overview

Description

  • Temperature limits:
    -40 ... +350°C for type T
    -40 ... +750°C for type J
    -40 ... +900°C for type E
    -40 ... +1000°C for type K (see table for sheath diameters)
  • Tolerance (IEC standard 584.2/Class 2):
    for T:
    ± 1°C (-40 ... +133°C)
    ± 0.0075 [t] (t > +133°C)
    for J, E, K:
    ± 2,5°C (-40 ... +333°C)
    ± 0.0075 [t] (t > +333°C)
  • Ceramic insulation of the thermocouple element
  • Application versatility

Main features & overview

04 tc8

Overview

Description

  • Temperature limits:
    -40 ... +750°C for type J
    -40 ... +900°C for type E
    -40 ... +1000°C for type K
    (see table for sheath diameters)
  • Tolerance (IEC standard 584.2/Class 2):
    ± 2,5°C (-40 ... +333°C)
    ± 0.0075 [t] (t > +333°C)
  • Ceramic insulation of the thermocouple element
  • Application versatility

Main features & overview

05 tc9

Overview

Description

  • Temperature limits:
    - 40 ... + 1200° C for type K
    0 ... + 1400° C for type S - R
    +600 ... + 1600° C for type B
    (see table for sheath diameters)
  • Tolerance (IEC standard 584.2/Class 1):
    for type K:
    ± 2.5° C (- 40 ... + 333° C)
    ± 0.0075 x [t] (t > + 333° C)
    for type S, R,
    ± 1° C 0...+1100
    ± [1+0,003 x (t -1100)]°C +1100...+1600°C
    for type B:
    +600° C ... + 1700°C
    ± 0.0025 x [t]
  • Ceramic insulation of the thermocouple element
  • Application versatility

Main features & overview

06 tc10

Overview

Description

  • Temperature limits:
    -40 ... +750°C for type J
    -40 ... +1200°C for type K
    (see table for sheath diameters)
  • Tolerance (IEC standard 584.2/Class 2):
    ± 2,5°C (-40 ... +333°C)
    ± 0.0075 [t] (t > +333°C)
  • Ceramic insulation of the thermocouple element
  • Suitable for direct insertion into molten metal

Main features & overview

02 tc6 ac6

Overview

Description

  • Temperature limits:
    -40 ... +350°C for type T
    -40 ... +750°C for type J
    -40 ... +900°C for type E
    -40 ... +1000°C for type K
    (see table for sheath diameters)
  • Tolerance (IEC standard 584.2/Class 2):
    for T:
    ± 1°C (-40 ... +133°C)
    ± 0.0075 [t] (t > +133°C)
    for J, E, K:
    ± 2,5°C (-40 ... +333°C)
    ± 0.0075 [t] (t > +333°C)
  • Ceramic insulation of the thermocouple element
  • Application versatility

Main features & overview

04 tc8

Overview

Amplified output - Steel industry

Description

  • Amplified output signal
    Temperature limits:
    - 40 ... + 750° C per tipo J
    - 40 ... + 900° C per tipo E
    - 40 ... + 1000° C per tipo K
    (see table for sheath diameters)
  • Tolerance (IEC standard 584.2/Class 2):
    ± 2.5° C (- 40 ... + 333° C)
    ± 0.0075 [t] (t > + 333° C)
  • Ceramic insulation of the thermocouple element
  • Application versatility

Main features & overview

05 tc9

Overview

Amplified output and ceramic sheath - Steel industry

Description

  • Amplified output signal
  • Temperature limits:
    -40 ... +1200°C for type K
    0 ... +1400°C for types S and R
    +600 ... +1600°C for type B
    (see table for sheath diameters)
  • Tolerance (IEC standard 584.2/Class 1):
    for type K:
    ± 2.5° C (- 40 ... + 333° C)
    ± 0.0075 x [t] (t > + 333° C)
    for type S, R,
    ± 1° C 0...+1100
    ± [1+0,003 x (t -1100)]°C +1100...+1600°C
    for type B:
    +600° C ... + 1700°C
    ± 0.0025 x [t]
  • Ceramic insulation of the thermocouple element
  • Application versatility

Main features & overview

01 show DIN A

Overview

Accessories: cables, protective sheathings, fittings, heads, amplifiers, adapter , display, remote inputs, connectors

Description

  • Extension and compensation cables for Thermocouples
  • Protective sheathings
  • Sliding compression fittings
  • Connection heads
  • 4-20ma signal amplifiers
  • Adapter for 4-20ma signal amplifiers
  • Display
  • IP67 remote temperature inputs on CANpen fieldbus
  • Connectors
FaLang translation system by Faboba